single-produkty.php
PRODUCTS

Base separator – Safety transducer

Base separator - safety transducer (3A) on DIN rail - safety class SIL 3 (TUV)
Application

Ensures insulation input / output. Processing of the lock signal from the system, mushroom breaker, etc. to SPDT NO transducer with loading 3A. Control of the safety circuits (e.g. locking electrovalves, emergency breakers, etc.)

SIL function

Implements SIL 3 function for NE or ND loading
– for NE loading, it shuts them down by switching off the input
– for ND loading, it switches them on by switching on the input

Technical data:

Hide the table
No.
1
2
3
4
5
6
7
 
Input signal
Output signal
Power supply
Attestations
Characteristic
Safety class SIL (Safety Integrity Level)
Options / functions
 
20.4...27.6 Vdc, protection against reverse polarization
DPST NO transducer, max. parameters: 3A 250Vac 750VA, 3A 125Vdc 120W
(resistance load) / reaction time 3 ms / max. 10 Hz
Input loop supply
ATEX- IMQ 09 ATEX 013X, ,FM & FM-C, TUV certificate SIL3 acc. to IEC61508
Ex II 3G nAC IIC T4
SIL3 even up to 10 years (TUV certificate No. C-IS-183645-01)
Single-channel D1092S or double-channel D1092D version
X

Log in to download this file.