single-produkty.php
PRODUCTS

D5290S-078 – Separator – Safety transducer

Separator – safety transducer (5A) with input line / low voltage / short-circuit monitoring, safety class SIL3
Application

Ensures insulation input / output. Processing of the lock signal from the system, mushroom breaker, etc. to SPDTx2 and SPSTx2 transducers. Has the option to select circuit monitoring type: input line monitoring (pulsating test), monitoring of voltage or monitoring of short-circuit, using DIP switches.

 

SIL function

Implements many SIL functions depending on the applied configuration of contact, both for NE and ND loads.

Technical data:

Hide the table
No.
1
2
3
4
5
6
7
 
Input signal
Output signal
Power supply
Attestations
Characteristic
Safety class SIL (Safety Integrity Level)
Options / functions
 
21.6...27.6 Vdc, protection against reverse polarization
SPDT + SPST potential-free transducer, max. parameters: 4A 250Vac 1000VA, 4A 250Vdc 120W
(resistance load) / reaction time 6 ms / max. 10 Hz
Input loop supply
ATEX acc. to EN60079-15, IECEx
ATEX: Ex II 3G nA nC IIC T4 Gc, IECEx: Ex nA nC IIC T4 Gc
SIL2/SIL3 acc. to IEC 61508
Standard DIN rail installation, dedicated installation plates
X