D5290S – Separator – Safety transducer

Separator – safety transducer (4A) with input line / low voltage monitoring, safety class SIL3 (TUV)
Application

High contact loading capacity separator 10A Ensures insulation input / output. Processing of the lock signal from the system, mushroom breaker, etc. to SPDT and SPST transducers. Has the option to select circuit monitoring type: input line monitoring (pulsating test), monitoring of low voltage or monitoring of short-circuit, using DIP switches.

SIL function

Implements SIL 3 function for NE loading (normal supply)
– switching off the input shuts down the load

Technical data:

Hide the table
No.
1
2
3
4
5
6
7
 
Input signal
Output signal
Power supply
Attestations
Characteristic
Safety class SIL (Safety Integrity Level)
Options / functions
 
21.6...27.6 Vdc, protection against reverse polarization
SPDT + SPST potential-free transducer, max. parameters: 4A 250Vac 1000VA, 4A 250Vdc 120W
(resistance load) / reaction time 6 ms / max. 10 Hz
Input loop supply
BVS 10 ATEX E 114, IECEx, Russian and Ukrainian acc. to GOST
ATEX: Ex II 3G nA nC IIC T4 Gc, IECEx: Ex nA nC IIC T4 Gc
SIL2/SIL3 (TUV certificate No. C-IS-204194-01)
Standard DIN rail installation, dedicated installation plates